MicroNode™ I/O is a high density, compact and economical I/O solution for popular DeviceNet™, Profibus®, EtherCAT®, and Ethernet based fieldbus networks. Additionally, the Ethernet versions contain cLogic™, an on-board C-compiler to handle the distribution of real-time logic tasks. Micronode™ I/O products reduce network and main controller bandwidth limits by offloading time critical tasks.
- Built-in cLogic™ compiler allows low level sequence execution, I/O ramping and limited filtering
- A mixture of Digital and Analog I/O makes selection of a cost-effective product easy
- The MicroNode™ I/O package design and options makes installation flexible
- IP 61 rated for use in harsh industrial environments
- Embedded web servers provide a graphical user interface for setup and diagnostics with a web browser See All Features
| Compare | Description | Drawings, CAD & Specs | Avail. | Price | ||
|---|---|---|---|---|---|---|
![]() | AS08482G-06Networked IO, MicroNode, EtherCAT, Combo IO, Digital Sink | |||||
![]() | AS00124R-08Networked IO, MicroNode, DeviceNet, Combo IO, Digital Sink, Front Connector | |||||
![]() | AS00127R-08Networked IO, MicroNode, DeviceNet, Combo IO, Digital Source, Front Connector |
Specifications
- TypeCompact Networked I/O
- Power RequirementsMinimum for Network and CPU: 24 VDC, 120 mA
AIO Power: Internal ±15 VDC; 50 mA. - Digital I/ODIDO: Each point either digital input or output (except for Profibus Combo)
Inputs: Optocoupler, 1.5 mA minimum, 1.5 msec filtering
Outputs: Open collector, 200mA maximum/channel
Max Output Current: 800 mA maximum on DIO 0-7, 800 mA maximum on DIO 8-15
Isolation: 500V optical isolation between CPU and digital I/O - Analog InputInputs: Single-ended analog inputs
Input Range: Software selectable (0 to 10 V), (-5 to +5 V)
Resolution: 12-bit; 16-bit (ECAT MicroNode model only)
Filtering: 16 Hz
Protection: ±15 V over-voltage protection
Non-linearity: ±3 bit (0.0732%)
Offset Error: ±10 mV (0.2%)
Gain Error: ±0.5%
Impedance: 10 kOhm minimum at 10 V - Analog OutputOutputs: Single-ended analog outputs
Output Range: -10 to +10V
Resolution: 12-bit; 16-bit (ECAT MicroNode model only)
Output Current: 5 mA/channel into a 2 kOhm load
Offset Error: ±2 LSB (~5 mV)
Gain Error: ±0.4% - Front Panel IndicatorsNetwork, Module: DeviceNet bi-color (red/green) status LEDs
Digital I/O Points: Green status LEDs
Rotary Switches: Node Address, Baud Rate (DeviceNet only)
- Operating Temperature0 to +55°C
- Storage Temperature-40 - 85°C
- Humidity5 to 95% non-condensing
- Weight0.44 lb (200 g)
0.661 lb (300 g) ECAT MicroNode model only - Dimensions3.150 x 4.724 x 1.142 in. (80 x 120 x 29 mm)
4.921 x 2.066 x 3.633 in. (125 x 52.5 x 92.3 mm) ECAT MicroNode model only
Features
EtherCAT I/O Modules
MicroNode™ EtherCAT® Networked Input/Output Controller provides a high density, compact and economical solution for 16 digital inputs/outputs, 8 analog inputs, and 4 analog outputs on the popular EtherCAT network. The 16 digital IO points are sinking, isolated, and can be used as either inputs or outputs. MicroNode™ EtherCAT contains all required object models, connectivity and configuration.
DeviceNet I/O Modules
MicroNode DeviceNet is ODVA Semi SIG compliant, implementing all required object models, connectivity and configuration. Supports Explicit Messaging and Polled I/O. Connect using 5 pole microfast type connection, and set MAC ID/Baud rate using rotary switches located on the front panel.
DeviceNet units also have the option of powering the I/O directly from the network bus power, via end user jumper configuration. See the user manual for instructions.
Mounting and Connection
Each MicroNode contains options for I/O connector placement and mounting feet. The D-sub 37 I/O connector is located on the front face or on the side, whichever configuration best meets your requirements. Mounting feet can be located to face front or back. Package size is only 80 x 120 x 29 mm.
Resources
Literature
MicroNode™ I/O with DeviceNet™, Profibus®, & Ethernet for Fieldbus Networks(167.5 kB, PDF) MicroNode™ EtherCAT for Fieldbus Networks(447.4 kB, PDF)
Manuals
MicroNode™ I/O DeviceNet™ COMBO Manual(211.2 kB, PDF) MicroNode™ I/O DeviceNet™ DIDO Manual(170.4 kB, PDF) MicroNode™ I/O Ethernet COMBO Manual(387.7 kB, PDF) MicroNode™ I/O Profibus COMBO Manual(261.5 kB, PDF) MicroNode™ I/O Ethernet DIDO Manual(389.5 kB, PDF) MicroNode™ I/O Networked I/O Pin-outs(45.6 kB, PDF) MicroNode™ I/O Networked I/O Pin-outs(3.3 MB, PDF)
Technical Notes
Plug-N-Play EtherCAT® I/O Gateway(1.1 MB, PDF)
Device Description Files
MicroNode™ AS00124-03 Firmware: 2.001 EDS File(26.2 kB, EDS) MicroNode™ AS00124-01 Firmware: 1.001 EDS File(26.2 kB, EDS) MicroNode™ AS00124-01 Firmware: 2.001 EDS File(26.2 kB, EDS) MicroNode™ AS00124-04 Firmware: 2.001 EDS File(26.2 kB, EDS) MicroNode™ AS00127-01 Firmware: 2.002 EDS File(26.4 kB, EDS) MicroNode™ AS00260-02 Firmware 1.004 GSD File(2.3 kB, GSD) MicroNode™ AS00127-02 Firmware: 1.002 EDS File(26.4 kB, EDS) MicroNode™ AS00160-02 Firmware 1.004 GSD File(2.3 kB, GSD) MicroNode™ AS00127-02-1 Firmware: 1.002 EDS File(26.4 kB, EDS) MicroNode™ AS00127-03-1 Firmware: 1.002 EDS File(26.4 kB, EDS) MicroNode™ AS00612-01 Firmware 2.001 EDS File(26.2 kB, EDS) MicroNode™ AS00127-03 Firmware: 1.002 EDS File(26.4 kB, EDS) MicroNode™ AS08482G ESI File(93.4 kB, XML)